The short answer When an air conditioner is completely dead, the cause is usually outside the equipment: thermostat batteries, a tripped breaker, a switch someone flipped, or a full drain pan that has tripped the safety switch. In Houston the drain pan is the one people miss.
- Time
- 15 minutes
- You’ll need
- Batteries, a flashlight
- Cost
- Usually nothing
Start at the thermostat and work toward the equipment. Each step rules out one link in the chain.
Look at the thermostat
If the screen is blank, replace the batteries. If it has no batteries, it takes power from the system, and a blank screen means the system has no power: go to the next step.
If the screen works, set it to Cool and at least three degrees below the room temperature. Wait five minutes. Many thermostats delay a restart to protect the compressor.
Reset the breakers
There are two: one for the indoor unit (often labeled furnace or air handler) and one for the outdoor unit (AC or condenser). A tripped breaker sits in the middle. Push it fully off, then on.
Reset each one once only.
Find the service switches
Near the indoor unit there is usually a switch that looks like an ordinary light switch. It gets turned off by accident, especially in closets and attics.
Outside, the gray box on the wall beside the unit holds a disconnect. Check that it is pushed in and not sitting loose.
Check the drain pan
If the indoor unit is in the attic, look in the metal pan beneath it. Water in that pan lifts a float switch that shuts the system off before the ceiling gets wet. Some systems have the switch on the drain pipe itself instead.
If there is water, the drain line is clogged. Clear the drain line and the system will restart once the water is gone.
Close the access panel
A door switch cuts power when the panel on the indoor unit is off or crooked. If the filter was changed recently, reseat the panel.
Listen at the outdoor unit
Set the thermostat to cool and stand by the outdoor unit. A click followed by a hum, with nothing turning, points to a failed capacitor. Complete silence with the indoor fan running points to the contactor or the wiring between the two units.
Stop and call if
- A breaker trips again after one reset
- You smell burning, or see scorch marks at the unit or the panel
- The outdoor unit hums but nothing turns
- The drain pan is full and water is close to the ceiling
What it usually turns out to be
| Cause | Can you fix it? | What the repair involves |
|---|---|---|
| Clogged drain, tripped float switch | Often, yes. | Clearing the line. If it keeps clogging, the drain needs cleaning out properly or re-pitching. |
| Dead thermostat batteries | Yes. | New batteries. |
| Failed capacitor | No. It stores a charge even with the power off. | A quick part swap. |
| Burned contactor | No. | Part swap, usually on the same visit. |
| Blown low-voltage fuse | No. Something shorted to blow it. | Find the short first, then replace the fuse. |
| Failed transformer or control board | No. | Diagnosis, then the part. |
Questions people ask us
The AC died right after a storm. What happened?
Power surges and brief outages are hard on capacitors, contactors and control boards. Check the breakers first. If they are fine, the surge probably took out a part. See power’s back but the AC isn’t.
Is it safe to keep flipping the breaker?
No. One reset is reasonable. A breaker that trips again is reporting a short or an overloaded motor, and forcing it risks the wiring and the compressor.
The fan runs but there is no cooling. Is that the same problem?
No, that is a different fault. Follow AC blowing warm air instead.